Electrical harmonics (armónicos eléctricos)

Currents and voltages at frequencies that are multiples of 50 Hz and distort the electrical waveform. They are produced by electronic equipment such as LED drivers, variable speed drives, computers, chargers and UPS units, and can heat cables and trip protective devices.

What harmonics are

Harmonics are parts of the current or voltage at a frequency that is a multiple of the grid frequency, which in Spain is 50 Hz (60 Hz in the US): the third harmonic runs at 150 Hz, the fifth at 250 Hz and so on. Added to the main wave they distort it, and the clean sine wave is no longer clean.

What produces them

Non-linear loads, which draw current in bursts rather than smoothly:

  • LED drivers and old electronic fluorescent ballasts.
  • Variable speed drives for motors, pumps and lifts (elevators).
  • Computers, servers and office equipment.
  • EV chargers, solar inverters and UPS units.

In a home they rarely cause trouble. In offices, shops with lots of LED lighting, warehouses with drives or buildings full of equipment, they can.

Problems they cause

  • Neutral overheating on three-phase installations, because the third harmonic adds up on it.
  • Unexplained tripping of RCDs and MCBs.
  • Failures in capacitor banks, which can go into resonance.
  • Heating of transformers and motors and shorter equipment life.

How they are measured and corrected

A power quality analyser is installed for several days to measure total harmonic distortion (THD) against the UNE-EN 50160 supply quality standard. Then the neutral can be upsized, filters fitted, detuned capacitor banks chosen or high-immunity RCDs used. As a guide, an analyser study costs 250 to 600 euros. See power factor correction in Seville, Spain.