Bathroom zones 0, 1 and 2 (volúmenes del baño)
The zones that ITC-BT-27 defines around a bath or shower, numbered 0, 1 and 2, where switches, sockets and electrical equipment are restricted according to how close they are to water.
What the bathroom zones are
Water greatly lowers the body’s resistance and raises the risk of shock. So ITC-BT-27, the Spanish rule for rooms with a bath or shower, divides the space into zones (volúmenes) and sets what can go in each. British readers will recognise the idea from UK bathroom zones.
- Zone 0: inside the bath or shower tray. The most restrictive; equipment must be IPX7.
- Zone 1: above the bath or shower, up to 2.25 m from the floor. Only fixed equipment designed for it, IPX4 minimum.
- Zone 2: a 0.6 m band around zone 1, also up to 2.25 m high. More is allowed, IPX4 minimum.
- Zone 3: a 2.4 m band beyond zone 2. Sockets can go here, protected by a 30 mA RCD, with equipment at least IPX1.
Where a socket can go
Ordinary sockets go outside zones 0, 1 and 2, that is, more than 0.6 m from the edge of the bath or shower tray, protected by a 30 mA RCD. Exact distances depend on the shape of the bath or tray and whether there is a fixed screen, so we measure each bathroom.
Bonding
On top of the zones, ITC-BT-27 requires the metal parts of the bathroom (pipes, bath, wastes) to be linked by equipotential bonding connected to earth.
Swimming pools
ITC-BT-31 applies a similar system of zones 0, 1 and 2 to pools, with 12 V safety extra-low voltage in zones 0 and 1.
When to call an electrician
When renovating the bathroom, moving the shower or adding a heated towel rail, an extractor or a shower light, the zones must be respected. See bathroom electrics and renovation electrics in Seville, Spain.
Related services
Renovation electrics
If you are renovating your flat, renovation electrics in Seville, Spain are the moment to bring the installation up to the way you live today: new kitchen and bathroom circuits, fuse board, chases and conduits, light points where you need them and the boletín at the end. We work in coordination with your builder or renovation company.
Electric shocks from taps
If you get electric shocks from taps (faucets), the shower, the washing machine or the fridge, a metal part is live and the current is not being carried to earth. That is a real risk of electrocution. In Seville, Spain we check the earthing (grounding), the protective conductors and the insulation of your appliances to find the fault and remove it.
Related questions
Need an electrician in Seville, Spain?
Call us or send a WhatsApp message with a photo of the job. You get a fixed quote before any work starts.